International Trade Manager:

Miss Xu  +86 13559640543

The installation of intelligent target flowmeter is a matter of caution


1. Installation precautions

The tube diameter of the direct pipe section should be equal to that of the flowmeter. The diameter of the pipe diameter should be the same as that of the pipe diameter. The length of the upstream of the flow meter is generally not less than 6-20d, and it is determined that the downstream straight pipe segment is not less than 3-4d.

Is according to the horizontal position calibration, the flowmeter is generally installed in horizontal pipe is used, when must be installed in vertical pipe, must use weighing method for flow meter vertical install state calibrated, direction of flow shall be from bottom to top.

To facilitate the maintenance of the use and prevent the flow meter to enable unidirectional force, parallel installation of bypass pipeline. The downstream of the flowmeter is equipped with a drainage tube to facilitate the cleaning and purge of the instrument. It is more necessary to measure the dirty fluid or the media that can solidify and crystallize.

Target plate and the measuring tube (table) should coaxial installation, according to a certain diameter of the experiment proved that the target plate and pipe center if deviation from 1 mm up and down, may cause from 1% to 2% of the flow coefficient of deviation, but around 1 mm deviation, the effect is obvious;

When the explosion-proof TGF is installed, check whether there are explosion-proof marks and explosion-proof certificate. The explosion-proof equipment is in good condition.

For small-bore flowmeter, because the pipe diameter is small and the flowmeter is relatively heavy, to prevent the pipe deformation or vibration during work, the support flowmeter should be set up. There is no need for a large diameter flowmeter to set up a bracket.

2. Use precautions

Before the flow of fluid, the downstream valve of the meter should be closed first, and the upstream valve should be opened, and the flow into the flow meter. Then slowly open the downstream valve of the flow meter, and close the bypass valve, so that the fluid slowly increases, and avoid suddenly opening the valve impact target plate to damage the instrument.

After the long-term operation of the flowmeter, it is necessary to use the weight method to check whether the characteristics of the force converter are changed in addition to cleaning the target plate and measuring the scale of the pipe. Hanging method is applied in the center of the target plate with the same weight of gravity flow, adjust instrument, corresponding to the flow force of the upper limit of the flow meter, namely Fmax by type (16.6), other traffic point are related to weight, read the output signal, check the basic error of each point and linearity. The "hang weight method" is described in the manufacturer's instruction manual or other information.

The force of the fluid acting on the target plate is different from that of the hanging weight, so the weight method cannot replace the actual flow calibration completely. To obtain high precision, necessary solid flow calibration is required.

When copying or changing the target plate, pay attention to the machining accuracy of the target plate, otherwise the flow coefficient will be affected. The test data showed that when the TGF of beta =0.8 and the diameter DN= 25, if the target diameter was 0.03mm and the flow coefficient deviation was 1%, the machining accuracy and surface roughness of the target plate also had an influence on the flow coefficient.

Flow meter is running, if discover the output value, check the power conversion system is normal, may be due to the fluid flowing through the target board at its downstream vortex street, caused by vibration in the target bearing, it is about the size and velocity, medium physical parameters (density and viscosity) and so on, can be in force transformation and electrical signals take measures to improve the damping in the system.


24-hour consultation hotline

+86 0595-22421111

International Trade Manager:
Miss Xu  +86 13559640543